UPS Sizing for a CCTV / ELV Rack: VA, Battery Runtime and Heat Load (Worked Example + Excel Calculator)

When the power fails, the security system must keep recording. That means the UPS in the ELV rack has to be sized for the real load, the runtime the client expects, and the heat it adds to a small room. Here is the method I use on ELV projects.


Step 1: Add up the real load (watts)

Example rack for a 16-camera system:

- NVR: 60 W

- 24-port PoE switch: 30 W own consumption + 16 cameras x 8 W = 158 W

- Core switch: 40 W

- Router / firewall: 20 W

Total = 278 W


Step 2: Add growth margin

Add 25% for future cameras and devices: 278 x 1.25 = 347.5 W (call it 348 W).


Step 3: Convert to VA and choose the UPS

VA = W / power factor. With PF 0.9: 348 / 0.9 = 386 VA.

Do not run a UPS above about 80% of its rating: 386 / 0.8 = 483 VA.

Check BOTH ratings on the datasheet. A "600 VA" unit is often only 360 W; 80% of 360 W = 288 W, which is below 348 W, so it fails. A 1000 VA / 900 W unit is the right choice here.


Step 4: Battery energy for the required runtime

Battery Wh = Load W x runtime (h) / inverter efficiency / usable factor

For 30 minutes: 348 x 0.5 / 0.9 / 0.8 = 242 Wh

Remember that battery Ah ratings are usually given at the 20-hour rate. At a 30-minute discharge a lead-acid battery delivers much less (often around 55-60% of nameplate), so always confirm with the manufacturer's runtime or constant-power table, or add an external battery pack.


Step 5: Heat load for the room

Heat (BTU/h) = W x 3.412

Equipment: 348 x 3.412 = 1,187 BTU/h

UPS losses (about 10% of load, 35 W): 35 x 3.412 = 119 BTU/h

Total about 1,306 BTU/h. In a small closed ELV room this needs ventilation or a small split unit, otherwise the batteries age fast (every 8-10 °C above 25 °C roughly halves VRLA battery life).


Practical tips

- Use maximum PoE consumption (IR on, heaters on), not typical values.

- Put the NVR, PoE switches and the core network on the UPS; fire alarm and access control panels normally have their own batteries, sized to their own standards.

- Leave 20-30% free rack space (U) for growth and airflow.


Excel calculator

I put rack U fill, UPS kVA with power factor and growth, battery Wh for runtime and BTU/h heat into one workbook: ELV Rack, UPS & Heat Load Sizing Calculator (Excel) - https://payhip.com/b/d8Gjp


Free alternative: the Free ELV Quick Calculator (Lite) covers CCTV storage, PoE budget and DC voltage drop - https://payhip.com/b/PUG1b


All 8 ELV workbooks in one download (CCTV, access control, fire alarm, PA, cabling BoQ, rack/UPS and more): https://payhip.com/b/R0uyW


Related posts

- PoE Switch Power Budget: https://payhip.com/ChenYuELVTemplates/blog/elv-design-notes/poe-switch-power-budget-how-to-check-it-formula-worked-example-and-free-excel-calculator

- How to Calculate CCTV NVR Storage: https://payhip.com/ChenYuELVTemplates/blog/elv-design-notes/how-to-calculate-cctv-nvr-storage-formula-worked-example-and-free-excel-calculator

- DC Voltage Drop for 12V/24V CCTV and Access Control: https://payhip.com/ChenYuELVTemplates/blog/elv-design-notes/dc-voltage-drop-for-12v-24v-cctv-and-access-control-formula-cable-size-table-logic-and-free-excel-calculator

Related guides: Fiber Optic Link Loss Budget | Conduit and Cable Tray Fill | CCTV Pixel Density and DORI